Information List - Siemens SIPROTEC 4 7SJ61 Manual

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Functions
2.3 Dynamic Cold Load Pickup
Addr.
Parameter
1805
51c PICKUP
1806
51c TIME DIAL
1807
51c TIME DIAL
1808
50c-3 PICKUP
1809
50c-3 DELAY
1901
50Nc-2 PICKUP
1902
50Nc-2 DELAY
1903
50Nc-1 PICKUP
1904
50Nc-1 DELAY
1905
51Nc PICKUP
1906
51Nc T-DIAL
1907
51Nc T-DIAL
1908
50Nc-3 PICKUP
1909
50Nc-3 DELAY

Information List

2.3.4
No.
Information
1730
>BLOCK CLP
1731
>BLK CLP stpTim
1732
>ACTIVATE CLP
1994
CLP OFF
1995
CLP BLOCKED
1996
CLP running
1997
Dyn set. ACTIVE
76
C
Setting Options
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
0.25 .. 35.00 A; ∞
0.00 .. 60.00 sec; ∞
Type of
Comments
Informa-
tion
SP
>BLOCK Cold-Load-Pickup
SP
>BLOCK Cold-Load-Pickup stop timer
SP
>ACTIVATE Cold-Load-Pickup
OUT
Cold-Load-Pickup switched OFF
OUT
Cold-Load-Pickup is BLOCKED
OUT
Cold-Load-Pickup is RUNNING
OUT
Dynamic settings are ACTIVE
Default Setting
Comments
1.50 A
51c Pickup
7.50 A
0.50 sec
51c Time dial
5.00
51c Time dial
∞ A
50c-3 Pickup
∞ A
0.00 sec
50c-3 Time Delay
7.00 A
50Nc-2 Pickup
35.00 A
0.00 sec
50Nc-2 Time Delay
1.50 A
50Nc-1 Pickup
7.50 A
0.30 sec
50Nc-1 Time Delay
1.00 A
51Nc Pickup
5.00 A
0.50 sec
51Nc Time Dial
5.00
51Nc Time Dial
∞ A
50Nc-3 Pickup
0.00 sec
50Nc-3 Time Delay
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016