Siemens SIPROTEC 4 7SJ61 Manual page 389

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Addr. Parameter
1114A Op.I meas.<1%
1201
FCT 50/51
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
1211
51 IEC CURVE
1212
51 ANSI CURVE
1213A MANUAL CLOSE
1214A 50-2 active
1215A 50 T DROP-OUT
1216A 50-3 active
1217
50-3 PICKUP
1218
50-3 DELAY
1219A 50-3 measurem.
1220A 50-2 measurem.
1221A 50-1 measurem.
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Function
C
Setting Options
P.System Data
NO
2
YES
50/51 Overcur.
ON
OFF
50/51 Overcur. 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
50/51 Overcur.
0.00 .. 60.00 sec; ∞ 0.00 sec
50/51 Overcur. 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 5.00 A
50/51 Overcur.
0.00 .. 60.00 sec; ∞ 0.50 sec
50/51 Overcur. 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
50/51 Overcur.
0.05 .. 3.20 sec; ∞
50/51 Overcur.
0.50 .. 15.00 ; ∞
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
50/51 Overcur.
Always
with 79 active
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
with 79 active
50/51 Overcur. 1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞ ∞ A
50/51 Overcur.
0.00 .. 60.00 sec; ∞ 0.00 sec
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
Functions, Settings, Information
Default Setting
Comments
NO
Operational current
measurement < 1%
ON
50, 51 Phase Time Over-
current
2.00 A
50-2 Pickup
50-2 Time Delay
1.00 A
50-1 Pickup
50-1 Time Delay
1.00 A
51 Pickup
5.00 A
0.50 sec
51 Time Dial
5.00
51 Time Dial
Disk Emulation
Drop-out characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50-2 instant.
Manual Close Mode
Always
50-2 active
0.00 sec
50 Drop-Out Time Delay
Always
50-3 active
∞ A
50-3 Pickup
50-3 Time Delay
Fundamental
50-3 measurement of
Fundamental
50-2 measurement of
Fundamental
50-1 measurement of
F.2 Settings
389