Siemens SIPROTEC 4 7SJ61 Manual page 162

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Functions
2.11 Automatic Reclosing System 79
Addr.
Parameter
7150
50-1
7151
50N-1
7152
50-2
7153
50N-2
7154
51
7155
51N
7163
46
7164
BINARY INPUT
7165
3Pol.PICKUP BLK
7166
50-3
7167
50N-3
7172
67Ns-1
7173
67Ns-2
7174
67Ns TOC
7175
bef.1.Cy:67Ns-1
7176
bef.1.Cy:67Ns-2
162
Setting Options
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
YES
NO
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
Set value T=T
instant. T=0
blocked T=∞
Set value T=T
instant. T=0
blocked T=∞
Default Setting
Comments
No influence
50-1
No influence
50N-1
No influence
50-2
No influence
50N-2
No influence
51
No influence
51N
No influence
46
No influence
Binary Input
NO
3 Pole Pickup blocks 79
No influence
50-3
No influence
50N-3
No influence
67Ns-1
No influence
67Ns-2
No influence
67Ns TOC
Set value T=T
before 1. Cycle: 67Ns-1
Set value T=T
before 1. Cycle: 67Ns-2