between the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and
decrementing process is in idle state.
Disk emulation offers advantages when the behavior of the negative sequence protection must be coordi-
nated with other relays in the system based on electromagnetic measuring principles.
Logic
The following figure shows the logic diagram for the negative sequence protection function. The protection
may be blocked via a binary input. This resets pickup and time elements and clears measured values.
When the negative sequence protection criteria are no longer satisfied (i.e. all phase currents below 0.05 x
or at least one phase current is greater than 10 x Ι
Ι
Nom
tion function are reset.
[7sj80-schieflastschutz-20060109, 1, en_US]
Figure 2-31
The pickup of the definite time overcurrent protection can be stabilized by the configured dropout time 4012
46 T DROP-OUT. This time is started and maintains the pickup condition if the current falls below the
threshold. Therefore, the function does not drop out at high speed. The trip command delay time continues
running. After the dropout delay time has elapsed, the pickup is reported OFF and the trip delay time is reset
unless the threshold has been exceeded again. If the threshold is exceeded again during the dropout delay
time, the time is canceled. The trip command delay time continues running. Should the threshold value be
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Logic diagram of the unbalanced load protection
2.5 Negative Sequence Protection 46
) all pickups issued by the negative sequence protec-
Nom
Functions
89