Technical Data
4.19 User-defined Functions (CFC)
Task levels:
Behavior of inputs and outputs:
Table 4-3
Name
Input
X1
X2 to X120
Output
Y
Task levels:
Behavior of inputs and outputs:
Info:
General Limits
Description
Maximum number of all CFC charts
considering all task levels
Maximum number of all CFC charts
considering one task level
Maximum number of all CFC inputs
considering all charts
Maximum number of reset-resistant
flipflops
D_FF_MEMO
332
Recommendation: Into task levels PLC1_BEARB and PLC_BEARB, because
these levels are directly triggered.
Note: If you use thi block in the task levels MW_BEARB and SFS_BEARB, a
change of the SWITCH signal is only recognized if the signal lasts longer
than the processing cycle of the task level.
COUNTACTIVE – This block calculates the number of active inputs. It is a generic block in which
you can specify a number of summands between 2 and 120.
Type
BOOL
BOOL
UINT
Recommendation: Into task levels PLC1_BEARB and PLC_BEARB, because
these levels are directly triggered.
Note: If you use thi block in the task levels MW_BEARB and SFS_BEARB, a
change of the SWITCH signal is only recognized if the signal lasts longer
than the processing cycle of the task level.
The COUNTACTIVE block is used to convert two Boolean inputs X1 and
X2 to INTEGER (FALSE=0, TRUE=1), and add them. The addition result is
available at output Y.
In the context menu of the block you can increase the number of inputs
to a maximum of 120:
Limit
32
16
400
350
Description
Input value
Input value
Number of "TRUE" input values
Comment
If the limit is exceeded, the device rejects the parameter
set with an error message, restores the last valid param-
eter set and restarts using that parameter set.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
C53000-G1140-C210-6, Edition 05.2016
Default function
FALSE
FALSE
0
SIPROTEC 4, 7SJ61, Manual