2.8 Monitoring Functions
eliminate pickup upon transformer saturation – this function is only available in a Holmgreen-connection (see
also Section 2.1.3.2). Faults in the current circuits are recognized if
= | i
+ i
+ i
+ i
Ι
F
A
B
C
Σ I THRESHOLD (address 8106) and Σ I FACTOR (address 8107) are setting parameters. The component Σ
I FACTOR · Σ | Ι | takes into account the permissible current proportional ratio errors of the input transducers
which are particularly prevalent during large short-circuit currents
%.
[stromsummenueberwachung-020313-kn, 1, en_US]
Figure 2-43
An error in the current sum results in the message
function. Furthermore, a fault log is initiated for a period of 100 ms.
The monitoring can be switched off.
The monitoring is available subject to the following conditions:
The three phase currents are connected to the device (address 251 A, B, C, (Gnd))
The ground current of the current transformer neutral point is connected to the fourth current input (Ι
(Holmgreen-connection). This is communicated to the device in the Power System Data 1 via address 280
YES.
The fourth current input is normally designed for a Ι
type, this monitoring is not available.
The settings CT PRIMARY (address 204) and Ignd-CT PRIM (address 217) must be the same.
The settings CT SECONDARY (address 205) and Ignd-CT SEC (address 218) must be the same.
The following logic diagram illustrates the operational mode of the current sum monitoring.
122
| > Σ I THRESHOLD + Σ I FACTOR · Σ | Ι |
E
Current sum monitoring
(Figure
2-43). The dropout ratio is about 97
Failure Σ I (No. 162) and blocking of the protection
–transformer. In case of a sensitive transformer
4
C53000-G1140-C210-6, Edition 05.2016
)
4
SIPROTEC 4, 7SJ61, Manual