Siemens SIPROTEC 4 7SJ61 Manual page 185

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Addr.
Parameter
9022A
RTD 2 LOCATION
9023
RTD 2 STAGE 1
9024
RTD 2 STAGE 1
9025
RTD 2 STAGE 2
9026
RTD 2 STAGE 2
9031A
RTD 3 TYPE
9032A
RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
9035
RTD 3 STAGE 2
9036
RTD 3 STAGE 2
9041A
RTD 4 TYPE
9042A
RTD 4 LOCATION
9043
RTD 4 STAGE 1
9044
RTD 4 STAGE 1
9045
RTD 4 STAGE 2
9046
RTD 4 STAGE 2
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Setting Options
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
2.14 Temperature Detection via RTD Boxes
Default Setting
Comments
Other
RTD 2: Location
100 °C
RTD 2: Temperature Stage 1
Pickup
212 °F
RTD 2: Temperature Stage 1
Pickup
120 °C
RTD 2: Temperature Stage 2
Pickup
248 °F
RTD 2: Temperature Stage 2
Pickup
Not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage 1
Pickup
212 °F
RTD 3: Temperature Stage 1
Pickup
120 °C
RTD 3: Temperature Stage 2
Pickup
248 °F
RTD 3: Temperature Stage 2
Pickup
Not connected
RTD 4: Type
Other
RTD 4: Location
100 °C
RTD 4: Temperature Stage 1
Pickup
212 °F
RTD 4: Temperature Stage 1
Pickup
120 °C
RTD 4: Temperature Stage 2
Pickup
248 °F
RTD 4: Temperature Stage 2
Pickup
Functions