Siemens SIPROTEC 4 7SJ61 Manual page 391

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Addr. Parameter
1321A 50N-1 measurem.
1322A 51N measurem.
1330
50N/51N
1331
MofPU Res T/TEp
1701
COLDLOAD PICKUP ColdLoadPickup
1702
Start Condition
1703
CB Open Time
1704
Active Time
1705
Stop Time
1801
50c-2 PICKUP
1802
50c-2 DELAY
1803
50c-1 PICKUP
1804
50c-1 DELAY
1805
51c PICKUP
1806
51c TIME DIAL
1807
51c TIME DIAL
1808
50c-3 PICKUP
1809
50c-3 DELAY
1901
50Nc-2 PICKUP
1902
50Nc-2 DELAY
1903
50Nc-1 PICKUP
1904
50Nc-1 DELAY
1905
51Nc PICKUP
1906
51Nc T-DIAL
1907
51Nc T-DIAL
1908
50Nc-3 PICKUP
1909
50Nc-3 DELAY
2201
INRUSH REST.
2202
2nd HARMONIC
2203
CROSS BLOCK
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Function
C
Setting Options
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
50/51 Overcur.
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
OFF
ON
ColdLoadPickup
No Current
Breaker Contact
79 ready
ColdLoadPickup
0 .. 21600 sec
ColdLoadPickup
1 .. 21600 sec
ColdLoadPickup
1 .. 600 sec; ∞
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 50.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup 1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞ ∞ A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup
0.25 .. 35.00 A; ∞
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
50/51 Overcur.
OFF
ON
50/51 Overcur.
10 .. 45 %
50/51 Overcur.
NO
YES
Functions, Settings, Information
Default Setting
Comments
Fundamental
50N-1 measurement of
Fundamental
51N measurement of
50N/51N
Multiple of Pickup <->
T/TEp
OFF
Cold-Load-Pickup Func-
tion
No Current
Start Condition
3600 sec
Circuit Breaker OPEN
Time
3600 sec
Active Time
600 sec
Stop Time
10.00 A
50c-2 Pickup
50c-2 Time Delay
2.00 A
50c-1 Pickup
50c-1 Time Delay
1.50 A
51c Pickup
7.50 A
0.50 sec
51c Time dial
5.00
51c Time dial
∞ A
50c-3 Pickup
50c-3 Time Delay
7.00 A
50Nc-2 Pickup
50Nc-2 Time Delay
1.50 A
50Nc-1 Pickup
50Nc-1 Time Delay
1.00 A
51Nc Pickup
5.00 A
0.50 sec
51Nc Time Dial
5.00
51Nc Time Dial
∞ A
50Nc-3 Pickup
50Nc-3 Time Delay
OFF
Inrush Restraint
15 %
2nd. harmonic in % of
fundamental
NO
Cross Block
F.2 Settings
391