Information List - Siemens SIPROTEC 4 7SJ61 Manual

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Addr.
Parameter
1316A
50N-3 active
1317
50N-3 PICKUP
1318
50N-3 DELAY
1319A
50N-3 measurem.
1320A
50N-2 measurem.
1321A
50N-1 measurem.
1322A
51N measurem.
1330
50N/51N
1331
MofPU Res T/TEp
2201
INRUSH REST.
2202
2nd HARMONIC
2203
CROSS BLOCK
2204
CROSS BLK TIMER
2205
I Max

Information List

2.2.12
No.
Information
1704
>BLK 50/51
1714
>BLK 50N/51N
1718
>BLOCK 50-3
1719
>BLOCK 50N-3
1721
>BLOCK 50-2
1722
>BLOCK 50-1
1723
>BLOCK 51
1724
>BLOCK 50N-2
1725
>BLOCK 50N-1
1726
>BLOCK 51N
1751
50/51 PH OFF
1752
50/51 PH BLK
1753
50/51 PH ACT
1756
50N/51N OFF
1757
50N/51N BLK
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
C
Setting Options
Always
with 79 active
0.25 .. 35.00 A; ∞
0.00 .. 60.00 sec; ∞
Fundamental
True RMS
Instantaneous
Fundamental
True RMS
Fundamental
True RMS
Fundamental
True RMS
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
OFF
ON
10 .. 45 %
NO
YES
0.00 .. 180.00 sec
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Type of
Comments
Informa-
tion
SP
>BLOCK 50/51
SP
>BLOCK 50N/51N
SP
>BLOCK 50-3
SP
>BLOCK 50N-3
SP
>BLOCK 50-2
SP
>BLOCK 50-1
SP
>BLOCK 51
SP
>BLOCK 50N-2
SP
>BLOCK 50N-1
SP
>BLOCK 51N
OUT
50/51 O/C switched OFF
OUT
50/51 O/C is BLOCKED
OUT
50/51 O/C is ACTIVE
OUT
50N/51N is OFF
OUT
50N/51N is BLOCKED
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Comments
Always
50N-3 active
∞ A
50N-3 Pickup
0.00 sec
50N-3 Time Delay
Fundamental
50N-3 measurement of
Fundamental
50N-2 measurement of
Fundamental
50N-1 measurement of
Fundamental
51N measurement of
50N/51N
Multiple of Pickup <->
T/TEp
OFF
Inrush Restraint
15 %
2nd. harmonic in % of
fundamental
NO
Cross Block
0.00 sec
Cross Block Time
7.50 A
Maximum Current for
Inrush Restraint
37.50 A
Functions
69