Phase Rotation; Description; Setting Notes - Siemens SIPROTEC 4 7SJ61 Manual

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Functions

2.15 Phase Rotation

2.15
Phase Rotation
A phase rotation function via binary input and parameter is implemented in 7SJ61 devices.
Applications
Phase rotation ensures that all protective and monitoring functions operate correctly even with anti-
clockwise rotation, without the need for two phases to be reversed.

Description

2.15.1
General
Various functions of the 7SJ61 device only function correctly if the phase rotation of the currents is known,
e.g. unbalanced load protection and some measurement quantity monitoring functions.
If an "acb" phase rotation is normal, the appropriate setting is made during configuration of the Power System
Data.
If the phase rotation can change during operation (e.g. the direction of a motor must be routinely changed),
then a changeover signal at the routed binary input for this purpose is sufficient to inform the protective relay
of the phase rotation reversal.
Logic
Phase rotation is permanently established at address 209 PHASE SEQ. (Power System Data). Via the exclu-
sive- OR gate the binary input
[meldelogikdrehfeldumschaltung-090902-kn, 1, en_US]
Figure 2-72
Influence on Protective and Monitoring Functions
The swapping of phases directly impacts the calculation of positive and negative sequence quantities, as well
as phase-to-phase voltages via the subtraction of one phase-to-ground voltage from another and vice versa.
Therefore, this function is vital so that phase detection messages, fault values, and operating measurement
values are not correct. As stated before, this function influences the negative sequence protection function
and some of the monitoring functions that issue messages if the defined and calculated phase rotations do
not match.

Setting Notes

2.15.2
Setting the Function Parameter
The normal phase sequence is set at 209 (see Section
phase rotation is reversed temporarily, then this is communicated to the protection device using the binary
input
>Reverse Rot. (5145).
190
>Reverse Rot. inverts the sense of the phase rotation applied with setting.
Message logic of the phase rotation reversal
2.1.3 Power System Data
1). If, on the system side,
C53000-G1140-C210-6, Edition 05.2016
SIPROTEC 4, 7SJ61, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents