Pickup Voltages of BI1 to BI3
Table 3-8
Binary inputs
BI1
BI2
BI3
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 220 V and AC 115 V/ 230 V
Contact Mode for Binary Outputs BO1 and BO2
Table 3-9
for
Jumper
BO1
X41
BO2
X42
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Jumper settings for the pickup voltages of the binary inputs BI1 to BI3 on the processor board
A–CPU as from 7SJ61.../FF
Jumper
X21
X22
X23
Jumper settings for the contact mode of the relays BO1 and BO2 on the processor board A–
CPU as from 7SJ61.../FF
Open in quiescent state
(NO)
1-2
1-2
DC 88 V threshold
DC 19 V threshold
1)
3)
L
M
L
M
L
M
Closed in quiescent state
(NC)
2-3
2-3
Mounting and Commissioning
3.1 Mounting and Connections
DC 176 V threshold
H
H
H
Presetting
1-2
1-2
245