Siemens SIPROTEC 4 7SJ61 Manual page 250

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
Pickup Voltage of BI4 to BI11
Table 3-11
Binary inputs
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 220 V and AC 115 V/ 230 V
250
Jumper settings for pickup voltages of binary inputs BI4 to BI11 on the input/output board A–
I/O-2 as from 7SJ62.../FFBrückenstellung der Steuerspannungen der Binäreingänge BE4 bis
BE11 auf der Ein-/Ausgabebaugruppe A-I/O-2 ab 7SJ61.../FF
Jumper
X21
X22
X23
X24
X25
X26
X27
X28
DC 19 V threshold
DC 88 V threshold
1)
3)
L
M
L
M
L
M
L
M
L
M
L
M
L
M
L
M
DC 176 V threshold
H
H
H
H
H
H
H
H
SIPROTEC 4, 7SJ61, Manual