Siemens SIPROTEC 4 7SJ61 Manual page 396

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
7101
FCT 79
7103
BLOCK MC Dur.
7105
TIME RESTRAINT
7108
SAFETY 79 ready
7113
CHECK CB?
7114
T-Start MONITOR
7115
CB TIME OUT
7116
Max. DEAD EXT.
7117
T-ACTION
7118
T DEAD DELAY
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7139
External SYNC
7140
ZONE SEQ.COORD. 79M Auto Recl.
7150
50-1
7151
50N-1
396
Function
C
Setting Options
79M Auto Recl.
OFF
ON
79M Auto Recl.
0.50 .. 320.00 sec;
0
79M Auto Recl.
0.50 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
No check
Chk each cycle
79M Auto Recl.
0.01 .. 320.00 sec;
79M Auto Recl.
0.10 .. 320.00 sec
79M Auto Recl.
0.50 .. 1800.00 sec;
79M Auto Recl.
0.01 .. 320.00 sec;
79M Auto Recl.
0.0 .. 1800.0 sec; ∞ 1.0 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0 .. 9
79M Auto Recl.
0 .. 9
79M Auto Recl.
(Einstellmöglich-
keiten anwendung-
sabhängig)
79M Auto Recl.
YES
NO
OFF
ON
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
Default Setting
Comments
OFF
79 Auto-Reclose Function
1.00 sec
AR blocking duration after
manual close
3.00 sec
79 Auto Reclosing reset
time
0.50 sec
Safety Time until 79 is
ready
No check
Check circuit breaker
before AR?
0.50 sec
AR start-signal monitoring
time
3.00 sec
Circuit Breaker (CB)
Supervision Time
100.00 sec
Maximum dead time
extension
∞ sec
Action time
Maximum Time Delay of
Dead-Time Start
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground
Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground
Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground
Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground
Fault
1
Number of Reclosing
Cycles Ground
1
Number of Reclosing
Cycles Phase
none
Close command via
control device
NO
External 25 synchronisa-
tion
OFF
ZSC - Zone sequence
coordination
No influence
50-1
No influence
50N-1
SIPROTEC 4, 7SJ61, Manual