Information To A Substation Control Center; Statistics; Description - Siemens SIPROTEC 4 7SJ61 Manual

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

General Interrogation
The general interrogation which can be retrieved via DIGSI enables the current status of the SIPROTEC 4 device
to be read out. All messages requiring general interrogation are displayed with their present value.
Spontaneous Messages
The spontaneous messages displayed using DIGSI reflect the present status of incoming information. Each
new incoming message appears immediately, i.e. the user does not have to wait for an update or initiate one.
2.17.1.3

Information to a Substation Control Center

If the device has a serial system interface, stored information may additionally be transferred via this interface
to a centralized control and storage device. Transmission is possible via different transmission protocols.

Statistics

2.17.2
The number of trips initiated by the 7SJ61, the number of close commands initiated by the AR and the oper-
ating hours under load are counted.
An additional counter allows the number of hours to be determined in which the circuit breaker is positioned
in the "open" condition. Further statistical data can be gained to optimize the intervals for circuit breaker main-
tenance.
Furthermore, if the device is utilized as motor protection, statistical values regarding the operation of the
motor as well as the last 5 motor startups are available.
The counter and memory levels are secured against loss of auxiliary voltage.
During the first start of the protection device the statistical values are pre-defined to zero.
2.17.2.1

Description

Number of Trips
of Trips In order to count the number of trips of 7SJ61, the 7SJ61 relay has to be informed of the position of
the circuit breaker auxiliary contacts via binary inputs. Hereby, it is necessary that the internal pulse counter
#of TRIPs= is allocated in the matrix to a binary input that is controlled by the circuit breaker OPEN position.
The pulse count value "Number of TRIPs CB" can be found in the "Statistics" group if the option "Measured and
Metered Values Only" was enabled in the configuration matrix.
Number of Automatic Reclosing Commands
The number of reclosing commands initiated by the automatic reclosing function is summed up in separate
counters for the 1st and ≥ 2nd cycle.
Operating Hours
The operating hours under load are also stored (= the current value in at least one phase is greater than the
limit value BkrClosed I MIN set under address 212).
Hours Meter "CB open"
A meter can be realized as a CFC application if it adds up the number of hours in state "Circuit Breaker open"
similarly to the operating hours meter. The universal hours meter is linked to a respective binary input and
counts if the binary input is active. Alternatively, the undershooting of the parameter value 212 BkrClosed
I MIN may be used as a criterion for starting the meter. The meter can be set or reset. A CFC application
example for such meter is available on the Internet (SIPROTEC Download Area).
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Functions
2.17 Auxiliary Functions
195