7SJ61
Bridging Time for Failure/Short-Circuit
(in not energized operation)

Binary Inputs and Outputs

4.1.3
Binary Inputs
Variant
7SJ610*–
7SJ611*–
7SJ612*–
7SJ613*–
7SJ614*–
Rated Voltage Range
Current Consumption (independent of the control
voltage)
Pickup time
Switching Thresholds
For Nominal Voltages
For Nominal Voltages
for nominal voltages (only for modules with 3
switching thresholds)
Maximum admissible voltage
Impulse Filter on Input
Output Relays
Output Relay for Commands/Annunciations, Alarm Relay
Number and Information
Order variant
7SJ610*–
7SJ611*–
7SJ612*–
7SJ613*–
7SJ614*–
Switching capability CLOSE
Switching capability TRIP
Switching voltage
Admissible current per contact (continuous)
Admissible current per contact (close and hold)
Total Current on common path
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Approx. 3 VA
200 ms
Quantity
3 (configurable)
8 (configurable)
11 (configurable)
8 (configurable)
11 (configurable)
DC 24 V to 250 V, bipolar
approx. 1.8 mA
approx. 4 ms
Switching Thresholds, adjustable voltage range with
jumpers
DC 24 V/ 48 V/ 60 V/ 110 V/ 125 V
DC 110 V/ 125 V/ 220 V/ 250 V
DC 220 V/ 250 V and AC 115 V/
230 V
DC 300 V
220 nF Coupling Capacitor at 220 V with recovery time
> 60 ms
)
*
According to the Order Variant (allocatable);
Values in ( ): up to release .../DD
Schließer
S/Ö, umschaltbar
2 (4)
6 (8)
4 (6)
6 (8)
4 (6)
1000 W/VA
30 VA 40 W resistive 25 W
bei L/R ≤ 50 ms
DC 250 V/ AC 250 V
30 A for 0.5 s (NO contact)
5 A continuous, 30 A for 0.5 s
Technical Data
4.1 General Device Data
Approx. 7 VA
V high≥ DC 19 V
V low ≤ DC 10 V
V high ≥ DC 88 V
V low ≤ DC 44V
V high ≤ DC 176 V
V low ≤ DC 88 V
3 (1)
3 (1)
3 (1)
3 (1)
3 (1)
5 A
281