Settings - Siemens SIPROTEC 4 7SJ61 Manual

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Functions
2.13 Flexible Protection Functions

Settings

2.13.3
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
BLK f out of r
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T DROPOUT DELAY
0A
DROPOUT RATIO
0A
DROPOUT RATIO
180
C
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
YES
NO
Please select
Current
dV/dt rising
dV/dt falling
Binary Input
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Exceeding
Dropping below
Ia
Ib
Ic
In
In sensitive
In2
1A
0.03 .. 40.00 A
5A
0.15 .. 200.00 A
1A
0.03 .. 40.00 A
5A
0.15 .. 200.00 A
0.001 .. 1.500 A
2.0 .. 200.0 V
1A
0.5 .. 10000.0 VAR
5A
2.5 .. 50000.0 VAR
15 .. 100 %
4 .. 100 V/s
0.00 .. 3600.00 sec
0.00 .. 60.00 sec
0.70 .. 0.99
1.01 .. 3.00
Default Setting
Comments
OFF
Flexible Function
3-phase
Mode of Operation
YES
Block while Freq. is out of
range
Please select
Selection of Measured
Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Ia
Current
2.00 A
Pickup Threshold
10.00 A
2.00 A
Pickup Threshold
10.00 A
0.100 A
Pickup Threshold
110.0 V
Pickup Threshold
200.0 VAR
Pickup Threshold
1000.0 VAR
20 %
Pickup Threshold
60 V/s
Pickup Threshold
1.00 sec
Trip Time Delay
0.00 sec
Dropout Time Delay
0.95
Dropout Ratio
1.05
Dropout Ratio
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016