Siemens SIPROTEC 4 7SJ61 Manual page 187

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Addr.
Parameter
9076
RTD 7 STAGE 2
9081A
RTD 8 TYPE
9082A
RTD 8 LOCATION
9083
RTD 8 STAGE 1
9084
RTD 8 STAGE 1
9085
RTD 8 STAGE 2
9086
RTD 8 STAGE 2
9091A
RTD 9 TYPE
9092A
RTD 9 LOCATION
9093
RTD 9 STAGE 1
9094
RTD 9 STAGE 1
9095
RTD 9 STAGE 2
9096
RTD 9 STAGE 2
9101A
RTD10 TYPE
9102A
RTD10 LOCATION
9103
RTD10 STAGE 1
9104
RTD10 STAGE 1
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Setting Options
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
2.14 Temperature Detection via RTD Boxes
Default Setting
Comments
248 °F
RTD 7: Temperature Stage 2
Pickup
Not connected
RTD 8: Type
Other
RTD 8: Location
100 °C
RTD 8: Temperature Stage 1
Pickup
212 °F
RTD 8: Temperature Stage 1
Pickup
120 °C
RTD 8: Temperature Stage 2
Pickup
248 °F
RTD 8: Temperature Stage 2
Pickup
Not connected
RTD 9: Type
Other
RTD 9: Location
100 °C
RTD 9: Temperature Stage 1
Pickup
212 °F
RTD 9: Temperature Stage 1
Pickup
120 °C
RTD 9: Temperature Stage 2
Pickup
248 °F
RTD 9: Temperature Stage 2
Pickup
Not connected
RTD10: Type
Other
RTD10: Location
100 °C
RTD10: Temperature Stage 1
Pickup
212 °F
RTD10: Temperature Stage 1
Pickup
Functions