Electrical Hookup (Electrical Network) - AEMC PowerPad 3945-B User Manual

3-phase power quality analyzer
Table of Contents

Advertisement

4.1.5

Electrical Hookup (electrical network)

• Highlight ELECTRICAL HOOKUP with the
button.
The following screen will appear:
Single-Phase
3 Phase 3-Wire
• Choose the hookup type with the
• Press the
button to apply the new hookup selection.
Hookup Types:
Single or two-phase: The neutral current is not measured or calculated.
3 phase - 3 wire connection (3V, 3A):
On DELTA network: Only power totals are measured.
On WYE network: The neutral current is not calculated. It is necessary
3 phase - 4 wire connection (4V, 3A): The neutral current is available and
its value and waveform are displayed.
On WYE network:
NOTE: Neutral current is calculated, not measured, in the 4 wire hookup.
V1 must be connected in all hookups, since the display is synchronized from
V1 and the network frequency measured by V1.
Neutral current is calculated by adding, for each datapoint, each of the 3
measured phases of current. This assumes that all current flows through
neutral. This results in a 256 datapoint waveform. If the 3 phases of current
were balanced, the calculated neutral current would be 0 for every datapoint.
Power Quality Analyzer Model 3945-B
N
L1
N
L1
L2
L3
Powers per phase are displayed, but not valid.
to connect neutral (V) to obtain the power per phase.
Powers per phase are available.
07/25/02 10:26
N
L1
L2
Two-Phase
N
L1
L2
L3
3 Phase 4-Wire
Figure 4-3
and
buttons.
buttons, then press the
100%
33