Parameter Description - Basic Set Up

6. Parameter Description

6.1 US-Parameters

Password

Load defaults

Load confi guration

Select confi guration

With different passwords different parameter groups can be accessed
for advanced programming.
By selecting LoAd and pressing ENTER, all the LF parameters
are returned to the factory default values. Note the display will
automatically change to show the value of LF.99 upon successful
loading of the default values.
Adjustment value:
Displayed responses:
By selecting LoAd and pressing ENTER, the selected confi guration
fi le in US.10 and all the existing LF parameter values will be loaded
into the drive. Note: if the confi guration is changed in US.10, the LF
parameter values are returned to the factory default values. In this
case, this should be done before any programming of the drive is
carried out as all parameters will be cleared. The display will change
automatically to LF.99 upon successful loading of the confi guration.
The process may take several seconds.
Adjustment value:
Displayed responses:
This parameter allows the user to select which mode the drive will
operate in. The possibilities are closed loop induction motor, closed
loop permanent magnet motor, and low speed gearless modes. Select
from the list below and then load the confi guration fi le into the drive
through parameter US.4.
Adjustment value:
ICLSd = Closed loop induction
I9LSS = Closed loop induction gearless
PCLSd = Closed loop permanent magnet
P9LSS = Closed loop permanent magnet
LoAd = reset all LF parameters
PASS = default successful
bdPAS = default not successful
LoAd = Load Confi guration
Pro9 = Loading confi guration
PASS = Load successful
bdPAS = Load not successful
gearless
81