Parameter Description - Motor Data

Rated motor speed

Rated motor current

Rated motor frequency

Unit:
PM
Value range :
Default setting:
Adjustment value:
plate
For permanent magnet synchronous motors there is no slip.
Therefore the value entered must be exactly the synchronous
rotational speed based on the rated frequency as noted below.
With this there is no further adjustment necessary. Do not round
this value off to the nearest whole number. With this there is no
further adjustment necessary.
LF.13 x 120
LF.11 =
motor poles
OR
LF.11 x motor poles
LF.13 =
Enter the motor nameplate rated current (FLA).
IM
Unit:
Value range:
PM
Default setting:
Adjustment value:
plate
Enter the exact rated frequency of the motor.
IM
Unit:
Value range:
PM
Default setting :
Adjustment value:
LF.13 x 120
LF.11 =
motor poles
OR
LF.11 x motor poles
LF.13 =
rpm
10.0....6000.0 or 500.0
(based on confi guration mode)
1165.0 or 150.0
(based on confi guration mode)
in accordance with the motor name
120
ampere
1.0...1.1 x Inverter rated current
8.0 A
in accordance with the motor name
hertz
4.0...100.0 Hz
60.0 Hz
in accordance with the motor name plate
120
93