Gland Plate Holes - Control Techniques Commander SE Advanced User's Manual

Variable speed drive for 3 phase induction motors from 0.25kw to 37kw
Hide thumbs Also See for Commander SE:
Table of Contents

Advertisement

Figure 4-6 Commander SE size 5 power circuit layout
Figure 4-7 Method of powering up the Commander SE size 5 by the DC bus using the drives internal inrush resistor
Terminal 15
Contactor coil supply
must be wired through
the drive healthy relay
Terminal 16
NOTE
The source of the relay must NOT be changed from Drive Healthy. For relay ratings refer to the Commander SE User
Guide.
4.3

Gland plate holes

A slot has been provided in the gland plate of sizes 1 to 4 for control cables. One of the gland plate holes can be used for
control cables but this should be separate from any power cables.
Size 5 has a separate gland plate with two 22mm holes for the control cables.
Table 4-1 Gland plate hole dimensions
Drive size
1
2
3
4
5
Commander SE Advanced User Guide
Issue Number: 4
L1
L2
L3
Contactor
coil
Normally Open Auxiliary
contact must be hard
wired with the drive
enable on terminal 9
110V ac supply for soft
start contactor coil
Number of holes in power terminal gland plate
22mm
3
3
1
2
11
+DC bus
-DC bus
U
V
W
+
Soft start
DC Choke
contactor
NO
NC
NO
DC Supply with each
drive individually fused
27mm
2
2
Motor
-
109