Relay Control

The Relay Control tab provides the means to control the Intellix™ BMT 330 relays. By
default the Active relay on alarm is enabled. Thus the relays reflect the alarm
statuses:
 Relay 1 (Service) is energized by default. If a service alarm is on or Intellix™
BMT 330 loses power it will switch to OFF.
 Relay 2 (Warning) and Relay 3 (Alarm) are de-energized by default. If either of
their respective alarms is on, the corresponding relay will switch to ON.
Relays can be manually controlled by disabling the Active relay on alarm. Then the
relays are not synchronized with the alarm statuses; and the user can manually
switch the relays (by clicking on the relay switch icon and then click on
Write/Program).
NOTE: disabling the Active relay on alarm is used to install/test the relays wiring.
During operation Intellix™ BMT 330 requires it to be enabled; otherwise any service,
warning and/or alarm event will not reflect on the relays.