• During a reset or when continuing control at the end of operation
• When Hold/Clear Hold is assigned to an event input
● Advance
This operation command performs the advance operation. The setting
can be made only in setup area 0. An operation error will occur in the
following situations.
• When AT is being executed
• During standby status
• During a reset or when continuing control at the end of operation
● Setting Areas
Control operation is executed in setting area 0. In this state, you can
perform operations that are permitted only during control or those that
cause no problems even if control is in progress. These operations
include reading PVs, writing SPs, and change Run/Reset status.
Setting area 0, however, prohibits operations that affect control,
including writing data at the initial setting level. (Reading setting data is
always allowed.)
In setting area 1, control operation is stopped. In this state, you can
perform operations that are not allowed in setting area 0. These opera-
tions include writing data at the initial setting level.
At power-ON, the Digital Controller is set in setting area 0. To move to
setting area 1, use the "move-to-setting area 1" command. To return to
setting area 0, turn the power OFF and ON again, or use the "software
reset" command.
Power ON
Setting area 0
Control in progress
2.3 Detailed Description of the Services
Software reset command
Setting area 1
"Move-to-setting
area 1" command
Control stopped.