SECTION 3 Communications Data for CompoWay/F
Variable
Address
Parameter name
type
C3 (83)
0016
Event Input Assignment 1
C3 (83)
0017
Event Input Assignment 2
C3 (83)
0018
Event Input Assignment 3
C3 (83)
0019
Event Input Assignment 4
C3 (83)
001D
Standby Sequence Reset
C3 (83)
001E
Auxiliary Output 1 Open in Alarm
C3 (83)
001F
Alarm 1 Hysteresis
Note 1:
E5AN/EN-HT only.
Note 2:
Only with external communications.
3-8
Setting (monitor) value
H'00000000 (0): None
H'00000001 (1): Run (OFF)/reset (ON)
H'00000002 (2): Run (ON)/reset (OFF)
H'00000003 (3): Auto/manual switch
H'00000004 (4): Reset
H'00000005 (5): Run
H'00000006 (6): Hold/clear hold
H'00000007 (7): Hold
H'00000008 (8): Advance
H'00000009 (9): Program No. switch 0
H'0000000A (10): Program No. switch 1
H'0000000B (11): Program No. switch 2
H'0000000C (12): Invert direct/reverse operation
H'0000000D (13): Program SP mode/remote SP mode (See note 1.)
H'0000000E (14): Remote SP mode/fixed SP mode (See note 1.)
H'0000000F (15): Program SP mode/fixed SP mode
H'00000010 (16): 100% AT execute/cancel
H'00000011 (17): 40% AT execute/cancel
H'00000012 (18): Setting change enable/disable
H'00000013 (19): Communications writing enable/disable (See note 2.)
H'00000014 (20): Latch cancel
H'00000015 (21): Wait enable (ON)/disable (OFF)
H'00000000 to H'00000015 (0 to 21)
* Same as for Event Input Assignment 1.
H'00000000 to H'00000015 (0 to 21)
* Same as for Event Input Assignment 1.
H'00000000 to H'00000015 (0 to 21)
* Same as for Event Input Assignment 1.
H'00000000 (0): Condition A
H'00000001 (1): Condition B
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Level
Initial
setting
Advanced
function
setting
Initial
setting