SECTION 5 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byte
mode
mode
0E48
2E24
Extraction of Square Root
Enable
0E60
2E30
Travel Time
0F00
2F00
Alarm 1 Type
0F02
2F01
Alarm 1 Latch
0F04
2F02
Alarm 1 Hysteresis
0F06
2F03
Alarm 2 Type
0F08
2F04
Alarm 2 Latch
0F0A
2F05
Alarm 2 Hysteresis
0F0C
2F06
Alarm 3 Type (See note 1.)
0F0E
2F07
Alarm 3 Latch (See note 1.)
0F10
2F08
Alarm 3 Hysteresis (See note 1.) Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
0F18
2F0C
Standby Sequence Reset
0F1A
2F0D
Auxiliary Output 1 Open in
Alarm
0F1C
2F0E
Auxiliary Output 2 Open in
Alarm
0F1E
2F0F
Auxiliary Output 3 Open in
Alarm (See note 1.)
Note 1:
Not displayed on the Controller display when Alarm 3 is not assigned to the output.
5-10
Setting (monitor) value
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000003E7 (1 to 999)
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower limit alarm
H'00000002 (2):
Upper limit alarm
H'00000003 (3):
Lower limit alarm
H'00000004 (4):
Upper and lower limit range alarm
H'00000005 (5):
Upper and lower limit alarm with standby sequence
H'00000006 (6):
Upper limit alarm with standby sequence
H'00000007 (7):
Lower limit alarm with standby sequence
H'00000008 (8):
Absolute value upper limit alarm
H'00000009 (9):
Absolute value lower limit alarm
H'0000000A (10): Absolute value upper limit alarm with standby sequence
H'0000000B (11): Absolute value lower limit alarm with standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): RSP absolute value upper limit alarm
H'0000000F (15): RSP absolute value lower limit alarm
H'00000000 (0): OFF
H'00000001 (1): ON
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower limit alarm
H'00000002 (2):
Upper limit alarm
H'00000003 (3):
Lower limit alarm
H'00000004 (4):
Upper and lower limit range alarm
H'00000005 (5):
Upper and lower limit alarm with standby sequence
H'00000006 (6):
Upper limit alarm with standby sequence
H'00000007 (7):
Lower limit alarm with standby sequence
H'00000008 (8):
Absolute value upper limit alarm
H'00000009 (9):
Absolute value lower limit alarm
H'0000000A (10): Absolute value upper limit alarm with standby sequence
H'0000000B (11): Absolute value lower limit alarm with standby sequence
H'0000000C (12): No alarm function
H'0000000D (13): PV change rate alarm
H'0000000E (14): RSP absolute value upper limit alarm
H'0000000F (15): RSP absolute value lower limit alarm
H'00000000 (0): OFF
H'00000001 (1): ON
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Same settings as the alarm 2 type.
H'00000000 (0): OFF
H'00000001 (1): ON
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 (0): Condition A
H'00000001 (1): Condition B
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Level
Initial
setting
Advanced
function
setting
Initial
setting
Advanced
function
setting
Initial
setting
Advanced
function
setting
Initial
setting
Advanced
function
setting