Variable
Address
Parameter name
type
C3 (83)
000D
Alarm 1 Type
C3 (83)
000E
Alarm 2 Type
C3 (83)
000F
Alarm 3 Type (See note 1.)
C3 (83)
0010
Communications Unit No. (See note 2.)
C3 (83)
0011
Communications Baud Rate
(See note 2.)
C3 (83)
0012
Communications Data Length
(See note 2.)
C3 (83)
0013
Communications Stop Bits
(See note 2.)
C3 (83)
0014
Communications Parity (See note 2.)
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm occurrences
via the status data.
Note 1:
Not displayed on the Controller display when Alarm 3 is not assigned to the output.
Note 2:
After communications parameters have been changed, reset the Controller to enable them.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower limit alarm
H'00000002 (2): Upper limit alarm
H'00000003 (3): Lower limit alarm
H'00000004 (4): Upper and lower limit range alarm
H'00000005 (5): Upper and lower limit alarm with standby sequence
H'00000006 (6): Upper limit alarm with standby sequence
H'00000007 (7): Lower limit alarm with standby sequence
H'00000008 (8): Absolute value upper limit alarm
H'00000009 (9): Absolute value lower limit alarm
H'0000000A (10): Absolute value upper limit alarm with standby
sequence
H'0000000B (11): Absolute value lower limit alarm with standby
sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): RSP absolute value upper limit alarm
H'0000000F (15): RSP absolute value lower limit alarm
H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower limit alarm
H'00000002 (2): Upper limit alarm
H'00000003 (3): Lower limit alarm
H'00000004 (4): Upper and lower limit range alarm
H'00000005 (5): Upper and lower limit alarm with standby sequence
H'00000006 (6): Upper limit alarm with standby sequence
H'00000007 (7): Lower limit alarm with standby sequence
H'00000008 (8): Absolute value upper limit alarm
H'00000009 (9): Absolute value lower limit alarm
H'0000000A (10): Absolute value upper limit alarm with standby
sequence
H'0000000B (11): Absolute value lower limit alarm with standby
sequence
H'0000000C (12): No alarm function
H'0000000D (13): PV change rate alarm
H'0000000E (14): RSP absolute value upper limit alarm
H'0000000F (15): RSP absolute value lower limit alarm
Same settings as the alarm 2 type
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
H'00000007 (7): 7
H'00000008 (8): 8
H'00000001 (1): 1
H'00000002 (2): 2
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
Level
Initial
setting
Communi-
cations
setting