Omron E5CN-HT Communications Manual page 107

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Address
Parameter name
Four-byte
Two-byte
mode
mode
0F22
2F11
Alarm 1 ON delay
0F24
2F12
Alarm 2 ON delay
0F26
2F13
Alarm 3 ON delay (See note 1.)
0F2A
2F15
Alarm 1 OFF delay
0F2C
2F16
Alarm 2 OFF delay
0F2E
2F17
Alarm 3 OFF delay (See note 1.) H'00000000 to H'000003E7 (0 to 999)
1000
3000
PV/SP Display Screen Selection H'00000000 (0): Only PV/SP displayed (no No. 3 display).
1002
3001
MV Display Selection
1006
3003
Automatic Display Return Time
1008
3004
Display Refresh Period
1010
3008
Additional PV Display
1016
300B
MV Display
1018
300C
Move to Protect Level Time
101A
300D
PV Change Color
101C
300E
PV Stable Band
101E
300F
Auto/Manual Select Addition
1020
3010
Character Select
Note 1:
Not displayed on the Controller display when Alarm 3 is not assigned to the output.
5.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000001 (1): The PV/SP/Program No. or Segment No., and the PV/SP/
MV are displayed in order.
H'00000002 (2): The PV/SP/MV and PV/SP/Program No. or Segment No. are
displayed in order.
H'00000003 (3): Only the PV/SP/Program No. or Segment No. are displayed.
H'00000004 (4): Only the PV/SP/MV are displayed.
H'00000005 (5): The PV/SP/Program No. or Segment No., and the PV/SP/
Remaining segment time are displayed in order.
H'00000006 (6): The PV/SP/MV and PV/SP/Remaining Segment Time are
displayed in order.
H'00000007 (7): Only the PV/SP/Remaining segment time are displayed.
H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)
H'00000001 to H'0000001E (1 to 30)
H'00000000 (0): Orange
H'00000001 (1): Red
H'00000002 (2): Green
H'00000003 (3): Red to green: When ALM1 is ON
H'00000004 (4): Green to red: When ALM1 is ON
H'00000005 (5): Red to green to red:
H'00000006 (6): Green to orange to red: Within PV stable band: Orange
H'00000007 (7): Orange to green to red: Within PV stable band: Green
H'00000008 (8): Red to orange to green: Linked to program.
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
Within PV stable band: Green
Outside stable band: Red
Outside stable band: Green, red
Outside stable band: Orange, red
Rising: red, Constant: orange, Fall-
ing: green
Level
Advanced
function
setting
5-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents