SECTION 5 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byte
mode
mode
1022
3011
PV Status Display Function
1024
3012
SV Status Display Function
1100
3100
Communications Protocol Set-
ting (See note 1.)
1102
3101
Communications Unit No.
(See note 1.)
1104
3102
Communications Baud Rate
(See note 1.)
110A
3105
Communications Parity
(See note 1.)
110C
3106
Send Data Wait Time
(See note 1.)
1200
3200
PF Setting
1204
3202
Monitor/Setting Item 1
Note 1:
After communications parameters have been changed, perform a software reset or turn the power OFF and ON again, to
enable the changes.
5-12
Setting (monitor) value
H'00000000 (0):OFF
H'00000001 (1): Manual
H'00000002 (2): Reset
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 1 to 3 OR status
H'00000007 (7): Heater alarm
H'00000008 (8): Standby
H'00000000 to H'00000008 (0 to 8)
* Same as for PV Status Display Function.
H'00000000 (0): CompoWay/F
H'00000001 (1): Modbus
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): OFF
H'00000001 (1): RUN
H'00000002 (2): Reset
H'00000003 (3): Run/reset
H'00000004 (4): Hold/clear hold
H'00000005 (5): Advance
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): Alarm latch cancel
H'00000009 (9): Auto/manual switch
H'0000000A (10): Monitor/setting item
H'00000000 (0): Disable
H'00000001 (1): PV/SP/program No. or segment No.
H'00000002 (2): PV/SP/MV
H'00000003 (3): PV/SP/remaining segment time
H'00000004 (4): Proportional band
H'00000005 (5): Integral time
H'00000006 (6): Derivative time
H'00000007 (7): Alarm value 1
H'00000008 (8): Alarm value upper limit 1
H'00000009 (9): Alarm value lower limit 1
H'0000000A (10): Alarm value 2
H'0000000B (11): Alarm value upper limit 2
H'0000000C (12): Alarm value lower limit 2
H'0000000D (13): Alarm value 3
H'0000000E (14): Alarm value upper limit 3
H'0000000F (15): Alarm value lower limit 3
H'00000010 (16): Program No.
H'00000011 (17): Segment No.
H'00000012 (18): Elapsed program time
H'00000013 (19): Remaining program time
H'00000014 (20): Elapsed segment time
H'00000015 (21): Remaining segment time
Level
Advanced
function
setting
Communi-
cations
setting
Advanced
function
setting