SECTION 5 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byte
mode
mode
0D22
2D11
Standard or Heating/Cooling
0D24
2D12
Direct/Reverse Operation
0D26
2D13
Closed/Floating
0D28
2D14
PID ON/OFF
0D2C
2D16
Program Time Unit
0D2E
2D17
Time Setting/Gradient Setting
0D30
2D18
Gradient Time Setting Unit
0D32
2D19
PV Start
0D34
2D1A
Reset Operation
0E00
2E00
Transfer Output Type
0E0C
2E06
Control Output 1 Assignment
0E0E
2E07
Control Output 2 Assignment
Note 1:
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.
5-8
Setting (monitor) value
H'00000000 (0): Standard
H'00000001 (1): Heating/cooling
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
H'00000000 (0): Floating
H'00000001 (1): Closed
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
H'00000000 (0): Hours, minutes
H'00000001 (1): Minutes, seconds
H'00000000 (0): Time setting
H'00000001 (1): Gradient setting
H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000000 (0): SP-priority SP start
H'00000001 (1): Slope-priority PV start
H'00000000 (0): Stop control
H'00000001 (1): Fixed SP operation
H'00000000 (0): OFF
H'00000001 (1): Present SP
H'00000002 (2): PV
H'00000003 (3): MV (heating)
H'00000004 (4): MV (cooling)
H'00000005 (5): Valve opening
When control output 1 is a linear output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
When control output 1 is an ON/OFF output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm (See note 1.)
H'00000008 (8): Stage output
H'00000009 (9): Run output
H'0000000A (10): Time signal 1 output
H'0000000B (11): Time signal 2 output
H'0000000C (12): Work bit 1
H'0000000D (13): Work bit 2
H'0000000E (14): Work bit 3
H'0000000F (15): Work bit 4
H'00000010 (16): Work bit 5
H'00000011 (17): Work bit 6
H'00000012 (18): Work bit 7
H'00000013 (19): Work bit 8
When control output 2 is a linear output: H'00000000 to H'00000002 (0 to 2)
(Same as for Control Output 1 Assignment.)
When control output 2 is an ON/OFF output: H'00000000 to H'00000013 (0 to
19) (Same as for Control Output 1 Assignment.)