SECTION 3 Communications Data for CompoWay/F
Variable
Address
Parameter name
type
C3 (83)
0050
Auxiliary Output 1 Assignment
C3 (83)
0051
Auxiliary Output 2 Assignment
C3 (83)
0052
Character Select
C3 (83)
0055
Alarm SP Selection
C3 (83)
0056
Auxiliary Output 3 Assignment
C3 (83)
0057
Closed/Floating
C3 (83)
0058
Travel Time
C3 (83)
0059
PV Dead Band
C3 (83)
005B
Manual MV Limit Enable
C3 (83)
005C
Direct Setting of Position Proportional
MV
C3 (83)
005D
AT Calculated Gain
C3 (83)
005E
AT Hysteresis
C3 (83)
005F
Limit Cycle MV Amplitude
C3 (83)
0060
Remote SP Enable
C3 (83)
0061
Remote SP Upper limit
C3 (83)
0062
Remote SP Lower limit
C3 (83)
0063
SP Tracking
C3 (83)
0064
Remote SP Input Error Output
C3 (83)
0065
PID Set Automatic Selection Data
Note 1:
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.
3-12
Setting (monitor) value
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm (See note 1.)
H'00000008 (8): Stage output
H'00000009 (9): Run output
H'0000000A (10): Time signal 1 output
H'0000000B (11): Time signal 2 output
H'0000000C (12): Work bit 1
H'0000000D (13): Work bit 2
H'0000000E (14): Work bit 3
H'0000000F (15): Work bit 4
H'00000010 (16): Work bit 5
H'00000011 (17): Work bit 6
H'00000012 (18): Work bit 7
H'00000013 (19): Work bit 8
H'00000000 to H'00000013 (0 to 19)
* Same as for the Auxiliary Output 1 Assignment parameter.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): Present SP
H'00000001 (1): Segment SP
H'00000000 to H'0000000F (0 to 15)
* Same as for the Auxiliary Output 1 Assignment parameter.
H'00000000 (0): Floating
H'00000001 (1): Closed
H'00000001 to H'000003E7 (1 to 999)
H'00000000 to H'00007E90 (0 to 32400)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'00000064 (0.1 to 10.0)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'000003E7 (0.01 to 9.99)
H'00000032 to H'000001F4 (5.0 to 50.0)
H'00000000 (0): OFF
H'00000001 (1): ON
SP lower limit to SP upper limit
SP lower limit to SP upper limit
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): PV
H'00000001 (1): DV
H'00000002 (2): SP
Level
Advanced
function
setting
Advanced
function
setting
Initial
setting
Advanced
function
setting