Omron E5CN-HT Communications Manual page 47

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

● Move to Protect Level
This command moves to the "protect level" and can be accepted only in
setup area 0.When this command is issued in setup area 1, an
"operation error" will be generated, and the move to the protect level will
be prohibited.
◆ Moving to Protect Level in Manual Mode
When this operation command is issued in manual mode, an
"operation error" will be generated, and the move to the protect level
will be prohibited.
● Auto/Manual Switch
This operation command switches the mode to manual mode or
automatic mode, based on the related information setting. This
command can be accepted in setup area 0 only. An "operation error"
will be generated in the following instances:
• When the command is executed in "setup area 1"
• When auto/manual switching is disabled (not displayed)
When the Controller is switched to manual mode, the "manual manipu-
lated variable" will be displayed. When the Controller is switched from
manual mode to automatic mode, the operation level's first parameter
will be displayed. When the Controller is switched to manual mode
while already in manual mode, the command will be completed
normally and the display will not change (the contents will not be
refreshed).
Note:
When the auto/manual mode is switched with an operation
command through communications and the Controller is in RAM
write mode, the auto/manual status is not stored in non-volatile
memory. Consequently, if the Controller is restarted by performing
a software reset or turning the power OFF and ON again, the
auto/manual mode is set to the last saved status.
◆ Switching to Manual Mode during Auto-tuning
If the mode is switched during auto-tuning (AT), the AT will be
cancelled and the Controller will be switched to manual mode.
● Parameter Initialization
The present settings are returned to the default values and written to
non-volatile memory. This command can be accepted in setup area 1
only. When this command is issued in setup area 0, an "operation error"
will be generated.
2.3 Detailed Description of the Services
2-23

Advertisement

Table of Contents