Omron E5CN-HT Communications Manual page 105

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Address
Parameter name
Four-byte
Two-byte
mode
mode
0E18
2E0C
Event Input Assignment 3
0E1A
2E0D
Event Input Assignment 4
0E20
2E10
Auxiliary Output 1 Assignment
0E22
2E11
Auxiliary Output 2 Assignment
0E24
2E12
Auxiliary Output 3 Assignment
0E28
2E14
Transfer Output Upper Limit
0E2A
2E15
Transfer Output Lower Limit
Note 1:
E5AN/EN-HT only.
Note 2:
Only with external communications.
Note 3:
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.
Note 4:
The setting (monitor) range depends on the transfer output type setting. (For details, refer to SECTION 5 Parameter in
E5CN/AN/EN-HT Digital Controllers Program Type User's Manual (Cat. No. H169).)
5.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 to H'00000015 (0 to 21)
H'00000000 (0): None
H'00000001 (1): Run (OFF)/reset (ON)
H'00000002 (2): Run (ON)/reset (OFF)
H'00000003 (3): Auto/manual switch
H'00000004 (4): Reset
H'00000005 (5): Run
H'00000006 (6): Hold/clear hold
H'00000007 (7): Hold
H'00000008 (8): Advance
H'00000009 (9): Program No. switch 0
H'0000000A (10): Program No. switch 1
H'0000000B (11): Program No. switch 2
H'0000000C (12): Invert direct/reverse operation
H'0000000D (13): Program SP mode/remote SP mode (See note 1.)
H'0000000E (14): Remote SP mode/fixed SP mode (See note 1.)
H'0000000F (15): Program SP mode/fixed SP mode
H'00000010 (16): 100% AT execute/cancel
H'00000011 (17): 40% AT execute/cancel
H'00000012 (18): Setting change enable/disable
H'00000013 (19): Communications writing enable/disable (See note 2.)
H'00000014 (20): Latch cancel
H'00000015 (21): Wait enable (ON)/disable (OFF)
H'00000000 to H'00000015 (0 to 21)
* Same as for Event Input Assignment 3.
H'00000000 (0): Not assigned
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm (See note 3.)
H'00000008 (8): Stage output
H'00000009 (9): Run output
H'0000000A (10): Time signal 1 output
H'0000000B (11): Time signal 2 output
H'0000000C (12): Work bit 1
H'0000000D (13): Work bit 2
H'0000000E (14): Work bit 3
H'0000000F (15): Work bit 4
H'00000010 (16): Work bit 5
H'00000011 (17): Work bit 6
H'00000012 (18): Work bit 7
H'00000013 (19): Work bit 8
H'00000000 to H'00000013 (0 to 19) (Same settings as the Auxiliary Output 1
Assignment)
H'00000000 to H'0000000F (0 to 15) (Same settings as the Auxiliary Output 1
Assignment)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400) (See note 4.)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400) (See note 4.)
Level
Initial
setting
Advanced
function
setting
Initial
setting
5-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents