Omron E5CN-HT Communications Manual page 102

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

SECTION 5 Communications Data for Modbus
Address
Four-
Two-
Parameter name
byte
byte
mode
mode
1802
3801
No. of Segments Used (See note 1.)
1804
3802
Segment Selection (See note 1.)
1806
3803
Segment Type (See note 2.)
1808
3804
Segment SP (See note 2.)
180A
3805
Segment Slope (See note 2.)
180C
3806
Segment Time (See note 2.)
180E
3807
PID Set No. (See note 1.)
1810
3808
Alarm Value 1 (See note 1.)
1812
3809
Alarm Value Upper Limit 1 (See note 1.)
1814
380A
Alarm Value Lower Limit 1 (See note 1.)
1816
380B
Alarm Value 2 (See note 1.)
1818
380C
Alarm Value Upper Limit 2 (See note 1.)
181A
380D
Alarm Value Lower Limit 2 (See note 1.)
181C
380E
Alarm Value 3 (See note 1.)
181E
380F
Alarm Value Upper Limit 3 (See note 1.)
1820
3810
Alarm Value Lower Limit 3 (See note 1.)
1822
3811
Program Repetitions (See note 1.)
1824
3812
Program Link Destination No. (See note 1.)
1826
3813
Time Signal 1 Set Segment (See note 1.)
1828
3814
Time Signal 1 ON Time (See note 1.)
182A
3815
Time Signal 1 OFF Time (See note 1.)
182C
3816
Time Signal 2 Set Segment (See note 1.)
182E
3817
Time Signal 2 ON Time (See note 1.)
1830
3818
Time Signal 2 OFF Time (See note 1.)
0A00
2A00
Proportional Band (See note 3.)
0A02
2A01
Integral Time (See note 3.)
0A04
2A02
Derivative Time (See note 3.)
0A0A
2A05
MV Upper Limit (See note 3.)
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm occurrences via the
status data.
Note 1:
The set values for the program specified in the Program Selection parameter are accessed for the following parameters: No. of
Segments Used, Segment Selection, PID Set No., Alarm Values 1 to 3, Alarm Upper Limits 1 to 3, Alarm Lower Limits 1 to 3, Program
Repetitions, Program Link Destination No., Time Signal 1 and 2 Set Segments, Time Signal 1 and 2 ON Times, and Time Signal 1 and
2 OFF Times. Check the set value of the Program Selection parameter before accessing these parameters.
Note 2:
The set values for the program specified in the Program Selection parameter and the section specified in the Segment Selection
parameter are accessed for the following parameters: Segment Type, Segment SP, Segment Slope, and Segment Time. Check the set
values of the Program Selection parameter and the Segment Selection parameter before accessing these parameters.
Note 3:
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected PID set is fixed at
PID1.
5-6
Setting (monitor) value
H'00000001 to H'00000020 (32)
H'00000000 to H'0000001F (31)
H'00000000 (0): Ramp
H'00000001 (1): Soak
H'00000002 (2): Step
SP lower limit to SP upper limit
H'00000000 to H'00007E90 (0 to 32400)
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
H'00000000 to H'00000008 (0 to 8) (0): Automatic Selection
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
'00000000 to '0000270F (0 to 9999)
H'FFFFFFFF(−1): No link
H'00000000 to H'00000007 (0 to 7)
H'00000000 (0) to No. of segments used −1
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
H'00000000 (0) to No. of segments used −1
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
H'00000000 to H'00009959 (0.00 to 99.59) (hours, minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes, seconds)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
Standard, heating/cooling, position proportional (closed):
H'00000000 to H'00007E90 (0.0 to 3240.0)
Position proportional (floating): H'00000001 to H'00007E90
(0.1 to 3240.0)
H'00000000 to H'00007E90 (0.0 to 3240.0)
Standard: MV lower limit +0.1 to H'0000041A
(MV lower limit +0.1 to 105.0)
Heating/cooling: H'00000000 to H'0000041A (0.0 to 105.0)
Position proportional (closed): MV lower limit +0.1 to H'0000041A)
MV lower limit +0.1 to 105.0)
Level
Program
Adjustment