Variable
Address
Parameter name
type
C1 (81)
0000
Operation/Adjustment Protect
C1 (81)
0001
Initial Setting/Communications Protect
C1 (81)
0002
Setting Change Protect
C1 (81)
0003
Set Point (See note 1.)
C1 (81)
000D
Heater Burnout Detection 1
C1 (81)
0012
Temperature Input Shift
C1 (81)
0013
Upper Limit Temperature Input Shift
Value
C1 (81)
0014
Lower Limit Temperature Input Shift
Value
C1 (81)
0015
Proportional Band (See note 2.)
C1 (81)
0016
Integral Time (See note 2.)
C1 (81)
0017
Derivative Time (See note 2.)
C1 (81)
0018
Cooling Coefficient (See note 2.)
C1 (81)
0019
Dead Band
C1 (81)
001A
Manual Reset Value
C1 (81)
001B
Hysteresis (Heating)
C1 (81)
001C
Hysteresis (Cooling)
C1 (81)
001D
Heater Burnout Detection 2
C1 (81)
001E
HS Alarm 1
C1 (81)
001F
HS Alarm 2
C1 (81)
0021
Wait Band
Note 1:
This is a read-only parameter. To change the SP, edit the SP parameter for the SP mode.
• Program SP (PSP): C4 (84), segment SP at 0004 or segment SP for each program under DA (9A)
• Fixed SP (FSP): C1 (81), Fixed SP at 0033
Note 2:
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected PID
set is fixed at PID1.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000(0) to H'00000005(5)
0: No control
1: Run level (PV allowed, PV/SP allowed, others allowed), program level
allowed, adjustment level allowed, PID setting level prohib-
ited
2: Run level (PV allowed, PV/SP allowed, others allowed), program level
allowed, adjustment level prohibited, PID setting level pro-
hibited
3: Run level (PV allowed, PV/SP allowed, others allowed), program level
prohibited, adjustment level prohibited, PID setting level pro-
hibited
4: Run level (PV allowed, PV/SP allowed, others prohibited), program
level prohibited, adjustment level prohibited, PID setting
level prohibited
5: Run level (PV allowed, PV/SP prohibited, others prohibited), program
level prohibited, adjustment level prohibited, PID setting
level prohibited
H'00000000 (0): Move to initial setting/communications setting level is
allowed. (Move to advanced function setting level is dis-
played.)
H'00000001 (1): Move to initial setting/communications setting level is
allowed. (Move to advanced function setting level is not
displayed.)
H'00000002 (2): Move to initial setting/communications setting level is
prohibited.
H'00000000 (0): OFF (Changing of setup on Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on Controller display is prohib-
ited.)
SP lower limit to SP upper limit
H'00000000 to H'000001F4 (0.0 to 50.0)
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
Standard, heating/cooling, positional proportional (closed):
H'00000000 to H'00007E90 (0.0 to 3240.0)
Positional proportional (floating):
H'00000001 to H'00007E90 (0.1 to 3240.0)
H'00000000 to H'00007E90 (0.0 to 3240.0)
H'00000001 to H'0000270F (0.01 to 99.99)
Temperature: H'FFFFB1E1 to H'00007E90 (−1999.9 to 3240.0)
Analog: H'FFFFF831 to H'0000270F (−19.99 to 99.99)
H'00000000 to H'000003E8 (0.0 to 100.0)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000(0): OFF
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Level
Protect
Operation
Adjustment
3-3