Omron E5CN-HT Communications Manual page 39

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

(4) Response Code
Normal Completion
Response code
0000
Normal completion
Error Occurred
Response code
Error name
1002
Command too
short
1101
Area type error
1100
Parameter error
3003
Read-only error
2203
Operation error
Note:
For details on AT (auto-tuning), refer to the separate E5CN/AN/
EN-HT Digital Controllers Program Type User's Manual (Cat. No.
H169).
2.3 Detailed Description of the Services
Name
Description
No errors were found.
Cause
The command is too short.
The variable type is wrong.
• Bit position is not "00."
• The write data is out of the setting
range.
Variable type "C0" or "80" was written
to.
• The Communications Writing
parameter is set to "OFF" (dis-
abled).
• Attempted to write to a parameter
in setup area 1 from setup area 0.
• Attempted to write to a protect
parameter from other than the pro-
tect level.
• AT (auto-tuning) was in progress.
(See note.)
• Non-volatile memory error.
• The program number was written
during operation.
2-15

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents