Omron E5CN-HT Communications Manual page 59

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Variable
Address
Parameter name
type
C3 (83)
0020
Auxiliary Output 2 Open in Alarm
C3 (83)
0021
Alarm 2 Hysteresis
C3 (83)
0022
Auxiliary Output 3 Open in Alarm
(See note 1.)
C3 (83)
0023
Alarm 3 Hysteresis (See note 1.)
C3 (83)
0024
HB ON/OFF
C3 (83)
0025
Heater Burnout Latch
C3 (83)
0026
Heater Burnout Hysteresis
α
C3 (83)
0028
C3 (83)
002B
Input Digital Filter
C3 (83)
002C
Additional PV Display
C3 (83)
002D
MV Display
C3 (83)
002E
Automatic Display Return Time
C3 (83)
002F
Alarm 1 Latch
C3 (83)
0030
Alarm 2 Latch
C3 (83)
0031
Alarm 3 Latch (See note 1.)
C3 (83)
0032
Move to Protect Level Time
C3 (83)
0033
Input Error Output
C3 (83)
0034
Cold Junction Compensation Method
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm occurrences
via the status data.
Note 1:
Not displayed on the Controller display when Alarm 3 is not assigned to the output.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000000 to H'00000064 (0.00 to 1.00)
H'00000000 to H'0000270F (0.0 to 999.9)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000001E (1 to 30)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
Level
Advanced
function
setting
Initial
setting
Advanced
function
setting
Initial
setting
Advanced
function
setting
3-9