Connection To Line Power And Grounding - Danfoss FC 300 Design Manual

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

6. How to Install

6.3.2. Connection to Line Power and Grounding

1.
2.
3.
4.
6
5.
The line connection is fitted to the line switch if this is included.
110
NOTE
The plug connector for power is pluggable on the FC 300 up to 10 hp [7.5 kW].
Insert the two screws into the de-coupling plate, and then slide it into place and tighten
the screws.
Make sure the FC 300 is properly grounded. Connect to the ground connection (terminal
95). Use the screw from the accessory bag.
Place plug connector 91(L1), 92(L2), 93(L3) from the accessory bag onto the terminals
labeled MAINS at the bottom of the FC 300.
Attach the line wires to the line power plug connector.
Support the cable with the enclosed supporting brackets.
NOTE
Make sure that the line voltage corresponds to the given line voltage on the FC 300
nameplate.
IT Line
Do not connect 400 V adjustable frequency drives with RFI filters to line supplies
with a voltage between phase and ground of more than 440 V.
The ground connection cable cross-section must be at least 0.016 in.
2 x rated line wires terminated separately according to EN 50178.
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
FC 300 Design Guide
2
[10 mm
2
] or