Encoder Option Mcb - Danfoss FC 300 Design Manual

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

8. Options and Accessories
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP (GND = 0 V)
Voltage level, logic'1' PNP (GND = 0 V)
Voltage level, logic '0' NPN (GND = 24V)
Voltage level, logic '1' NPN (GND = 24 V)
Maximum voltage on input
Pulse frequency range
Duty cycle, min. pulse width
Input impedance
8.1.6. Analog inputs - Terminal X30/11, 12:
Analog input:
Number of analog inputs
Terminal number
Modes
Voltage level
Input impedance
Max. voltage
Resolution for analog inputs
Accuracy of analog inputs
8
Bandwidth
8.1.7. Digital outputs - Terminal X30/6, 7:
Digital output:
Number of digital outputs
Terminal number
Voltage level at digital/frequency output
Max. output current
Max. load
Max. capacitive load
Minimum output frequency
Maximum output frequency
Accuracy of frequency output
8.1.8. Analog output - Terminal X30/8:
Analog output:
Number of analog outputs
Terminal number
Current range at analog output
Max. load GND - analog output
Accuracy on analog output
Resolution on analog output

8.1.9. Encoder Option MCB 102

The encoder module can be used as feedback source for closed-loop flux control (par. 1-02), as
well as closed-loop speed control (par. 7-00). Configure encoder option in parameter group 17-
xx
152
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
FC 300 Design Guide
X30.2, X30.3, X30.4
PNP or NPN
0-24 V DC
< 5 V DC
> 10 V DC
< 14 V DC
> 19 V DC
28 V continuous
0-110 kHz
4.5 ms
> 2 kΩ
X30.11, X30.12
Voltage
0-10 V
> 10 kΩ
20 V
10 bit (+ sign)
Max. error 0.5% of full scale
FC 301: 20 Hz/ FC 302: 100 Hz
X30.6, X30.7
0-24 V
40 mA
≥ 600 Ω
< 10 nF
0 Hz
≤ 32 kHz
Max. error: 0.1% of full scale
X30.8
0 - 20 mA
500 Ω
Max. error: 0.5% of full scale
12 bit
2
2
1

Advertisement