Danfoss FC 300 Design Manual page 63

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Line Supply 3 x 200-240 VAC
FC
302
High/ Normal Load*
Output current
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
301/FC
P15K
HO
Typical
Shaft
15
Output [kW]
Enclosure IP 21
Enclosure IP 55,
66
Continuous
(3 x 200-240 V)
59.4
[A]
Intermittent
(60 sec overload)
89.1
(3 x 200-240 V)
[A]
Continuous
KVA (208 V AC)
21.4
[KVA]
Continuous
(3 x 200-240 V)
54
[A]
Intermittent
(60 sec overload)
81
(3 x 200-240 V)
[A]
Max. cable size
90 (3/0)
[mm
2
(AWG)]
2)
Max.
pre-fuses
125
[A]
1
Estimated power
loss
624
at
rated
max.
load [W]
4)
Weight,
enclosure IP 21,
IP 55, 66 [kg]
Efficiency
4)
0.964
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
P18K5
P22K
NO
HO
NO
HO
18.5
18.5
22
22
C1
C1
C1
C1
C1
C1
74.8
74.8
88
88
115
82.3
112
96.8
132
127
26.9
26.9
31.7
31.7
41.4
68
68
80
80
104
74.8
102
88
120
114
90 (3/0)
90 (3/0)
125
160
737
740
845
874
1140 1143 1353 1400 1636
45
45
45
0.965
0.965
4. FC 300 Selection
P30K
P37K
NO
HO
NO
HO
NO
30
30
37
37
45
C2
C2
C2
C2
115
143
143
170
173
157
215
187
41.4
51.5
51.5
61.2
104
130
130
154
156
143
195
169
120 (4/0)
120 (4/0)
200
250
65
65
0.966
0.966
4
63