4. FC 300 Selection
Line Supply 3 x 525-690 V AC
FC 302
High/ Normal Load*
Output current
4
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
70
P37K
HO
NO
Typical
shaft
output at 690 V
37
45
[kW]
Continuous
46
54
(at 690 V) [A]
Intermittent (60
sec overload)
74
59
(at 690 V) [A]
Continuous KVA
55
65
(at 690 V) [KVA]
Continuous
50
58
(at 690 V) [A]
Max. cable size
[mm
2
(AWG)]
Max. pre-fuses
80
[A]
1
Estimated pow-
er loss
1355
1458
at rated max.
4)
load [W]
Weight,
enclosure IP 21,
IP 54 [kg]
Weight,
enclosure IP 00
[kg]
Efficiency
4)
0.98
MG.33.B9.22 - VLT
®
P45K
P55K
P75K
HO
NO
HO
NO
HO
45
55
55
75
75
54
73
73
86
86
86
80
117
95
129
65
87
87
103
103
58
77
77
87
87
2x70 (2x2/0)
90
125
1459
1717 1721 1913 1913 2262 2264 2662
0.98
0.98
is a registered Danfoss trademark.
FC 300 Design Guide
P90K
NO
HO
NO
90
90
110
108
108
131
119
162
144
129
129
157
109
109
128
150
175
0.98
0.98