Danfoss FC 300 Design Manual page 68

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

4. FC 300 Selection
Line Supply 3 x 380-500 V AC
FC 302
High/ Normal Load*
4
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
68
P250
HO
NO
Typical shaft out-
250
315
put at 400 V [kW]
Typical shaft out-
350
450
put at 460 V [HP]
Typical shaft out-
315
355
put at 500 V [kW]
Enclosure IP 21
E1
Enclosure IP 54
E1
Enclosure IP 00
E2
Output current
Continuous
480
600
(at 400 V) [A]
Intermittent
(60
sec overload)
720
660
(at 400 V) [A]
Continuous
443
540
(at 460/ 500 V) [A]
Intermittent
(60
sec overload)
665
594
(at 460/ 500 V) [A]
Continuous KVA
333
416
(at 400 V) [KVA]
Continuous KVA
353
430
(at 460 V) [KVA]
Continuous KVA
384
468
(at 500 V) [KVA]
Continuous
472
590
(at 400 V) [A]
Continuous
436
531
(at 460/ 500 V) [A]
Max.
cable
size
2 x 185 (2 x 350
2
2)
mcm)
[mm
(AWG
)]
Max. pre-fuses [A]
700
1
Estimated
power
loss
6005
7630
at rated max. load
4)
[W]
Weight,
enclosure IP 21, IP
263
54 [kg]
Weight,
enclosure
IP
00
221
[kg]
Efficiency
4)
0.976
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
P315
P355
HO
NO
HO
NO
315
355
355
400
450
500
500
600
355
400
400
500
E1
E1
E1
E1
E2
E2
600
658
658
745
900
724
987
820
540
590
590
678
810
649
885
746
416
456
456
516
430
470
470
540
468
511
511
587
590
647
647
733
531
580
580
667
4x240 (4x500
4x240 (4x500
mcm)
mcm)
900
900
6960
7701
7691
8879
270
272
234
236
0.978
0.978
FC 300 Design Guide
P400
HO
NO
400
450
550
600
500
530
E1
E1
E2
695
800
1043
880
678
730
1017
803
482
554
540
582
587
632
684
787
667
718
4x240 (4x500
mcm)
900
7964
9428
313
277
0.980

Advertisement

Table of Contents
loading