4. FC 300 Selection
Line Supply 3 x 525-690 V AC
FC 302
High/ Normal Load*
4
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
72
P250
HO
Typical shaft output at
200
550 V [kW]
Typical shaft output at
300
575 V [HP]
Typical shaft output at
250
690 V [kW]
Output current
Continuous
303
(at 550 V) [A]
Intermittent (60 sec
overload)
455
(at 550 V) [A]
Continuous
290
(at 575/690 V) [A]
Intermittent (60 sec
overload)
435
(at 575/690 V) [A]
Continuous KVA
289
(at 550 V) [KVA]
Continuous KVA
289
(at 575 V) [KVA]
Continuous KVA
347
(at 690 V) [KVA]
Continuous
299
(at 550 V) [A]
Continuous
286
(at 575 V) [A]
Continuous
296
(at 690 V) [A]
2
2 x 185 (2 x 350
Max. cable size [mm
mcm)
(AWG)]
Max. pre-fuses [A]
1
500
Estimated power loss
at rated max. load [W]
4875
4)
Weight,
enclosure IP 21, IP 54
151
[kg]
Weight,
138
enclosure IP 00 [kg]
4)
Efficiency
0.981
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
P315
NO
HO
NO
HO
250
250
315
315
350
350
400
400
315
315
400
355
360
360
418
395
396
540
460
593
344
344
400
380
378
516
440
570
343
343
398
376
343
343
398
378
411
411
478
454
355
355
408
381
339
339
390
366
352
352
400
366
2 x 185 (2 x 350
2 x 185 (2 x 350
mcm)
600
5821
5185
6149
5383
165
151
0.984
FC 300 Design Guide
P355
NO
355
450
450
470
517
450
495
448
448
538
453
434
434
mcm)
700
6449
263
221
0.985