FC 300 Design Guide
6.5: Cable entry holes for enclosure B1. The sug-
gested use of the holes are purely recommenda-
tions and other solutions are possible.
6.6: Cable entry holes for enclosure B2. The sug-
gested use of the holes are purely recommenda-
tions and other solutions are possible.
Term.
no.
1)
Protected Ground Connection
96
97
98
99
U
V
W
PE
1)
U1
V1
W1
1)
PE
W2
U2
V2
U1
V1
W1
PE
1)
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
6.7: Cable entry holes for enclosure C1. The sug-
gested use of the holes are purely recommenda-
tions and other solutions are possible.
6.8: Cable entry holes for enclosure C2. The sug-
gested use of the holes are purely recommenda-
tions and other solutions are possible.
Motor voltage 0-100% of line voltage.
3 wires out of motor
Delta-connected
6 wires out of motor
Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected separately.
NOTE
When using motors without
phase insulation paper or other
insulation reinforcement suita-
ble for operation with voltage
supplied from adjustable fre-
quency drives, fit asine-wave fil-
ter on the output of the FC 300.
6. How to Install
6
115