9. RS-485 Installation and Set-up
The reference and MAV are scaled as follows:
9.6.4. PROFIdrive Control Profile
This section describes the functionality of the control word and status word in the PROFIdrive
profile. Select this profile by setting par. 8-10
9
9.6.5. Control Word according to PROFIdrive Profile (CTW)
The control word is used to send commands
from a master (a PC, for example) to a slave.
Explanation of the Control Bits
Bit 00, OFF 1/ON 1
Normal ramp stop using the ramp times of the actual selected ramp.
180
Control word profile to PROFIdrive
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
FC 300 Design Guide
.
Bit = 0
Bit = 1
OFF 1
ON 1
OFF 2
ON 2
OFF 3
ON 3
Coasting
No coasting
Quick stop
Ramp
Hold frequency
Use ramp
output
Ramp stop
Start
No function
Reset
Jog 1 OFF
Jog 1 ON
Jog 2 OFF
Jog 2 ON
Data invalid
Data valid
No function
Slow-down
No function
Catch up
Parameter set-up Selection lsb
Parameter set-up Selection msb
No function
Reverse