Danfoss FC 300 Design Manual page 169

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Bit 6 is not used
Bit 5 = 1: Broadcast, address bits (0-4) are not used
Bit 5 = 0: No Broadcast
Bit 0-4 = Adjustable frequency drive address 1-31
2. Address format 1-126:
Bit 7 = 1 (address format 1-126 active)
Bit 0-6 = Adjustable frequency drive address 1-126
Bit 0-6 = 0 Broadcast
The slave returns the address byte unchanged to the master in the response telegram.
9.4.5. Data Control Byte (BCC)
The checksum is calculated as an XOR-function. Before the first byte in the telegram is received,
the calculated checksum is 0.
9.4.6. The Data Field
The structure of data blocks depends on the type of telegram. There are three telegram types,
and the type applies for both control telegrams (master=>slave) and response telegrams
(slave=>master).
The three types of telegram are:
Process block (PCD):
The PCD is made up of a data block of four bytes (2 words) and contains:
- Control word and reference value (from master to slave)
- Status word and present output frequency (from slave to master).
Parameter block:
The parameter block is used to transfer parameters between master and slave. The data block is
made up of 12 bytes (6 words) and also contains the process block.
Text block:
The text block is used to read or write texts via the data block.
MG.33.B9.22 - VLT
®
is a registered Danfoss trademark.
9. RS-485 Installation and Set-up
9
169