Danfoss FC 300 Design Manual page 66

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

4. FC 300 Selection
Line Supply 3 x 380-500 V AC (FC 302), 3 x 380-480 V AC (FC 301)
FC 301/FC 302
High/ Normal Load*
4
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
66
P30K
HO
NO
Typical
Shaft
30
37
output [kW]
Enclosure IP 21
C1
Enclosure IP 55,
C1
66
Output
cur-
rent
Continuous
(3 x 380-440 V)
61
73
[A]
Intermittent (60
sec overload)
91.5
80.3
(3 x 380-440 V)
[A]
Continuous
(3 x 440-500 V)
52
65
[A]
Intermittent (60
sec overload)
78
71.5
(3 x 440-500 V)
[A]
Continuous KVA
(400
V
AC)
42.3
50.6
[KVA]
Continuous KVA
(460
V
AC)
51.8
[KVA]
Continuous
(3 x 380-440 V)
55
66
[A]
Intermittent (60
sec overload)
82.5
72.6
(3 x 380-440 V)
[A]
Continuous
(3 x 440-500 V)
47
59
[A]
Intermittent (60
sec overload)
70.5
64.9
(3 x 440-500 V)
[A]
Max. cable size
90 (3/0)
2
2)
[mm
(AWG
)]
Max. pre-fuses
100
[A]
1
Estimated pow-
er loss
570
698
at rated max.
4)
load [W]
Weight,
enclosure IP 21,
45
IP 55, 66 [kg]
4)
0.983
Efficiency
MG.33.B9.22 - VLT
®
P37K
P45K
P55K
HO
NO
HO
NO
HO
37
45
45
55
55
C1
C1
C1
C1
73
90
90
106
106
110
99
135
117
159
65
80
80
105
105
97.5
88
120
116
158
50.6
62.4
62.4 73.4
73.4
63.7
83.7
66
82
82
96
96
99
90.2
123
106
144
59
73
73
95
95
88.5
80.3
110
105
143
90 (3/0)
90 (3/0)
120 (4/0)
125
160
697
843
891 1083 1022 1384 1232 1474
45
45
0.983
0.982
0.983
is a registered Danfoss trademark.
FC 300 Design Guide
P75K
NO
HO
NO
75
75
90
C2
C2
C2
C2
147
147
177
162
221
195
130
130
160
143
195
176
102
102
123
104
128
133
133
161
146
200
177
118
118
145
130
177
160
120 (4/0)
250
250
65
65
0.985

Advertisement

Table of Contents
loading

Table of Contents