13.9
13.9.1
Technical manual
activated outputs OUTx where 1≤x≤16. The values represented by the different OUTx
are according to Table 340. When an OUTx is not activated, its value is 0.
The IB16FCVB function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Table 340:
Outputs and their values when activated
Name of OUTx
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted to boolean by
the IB16FCVB function block.
The operator position input (PSTO) determines the operator place. The integer
number that is communicated to the IB16FCVB can only be written to the block while
the PSTO is in position "Remote". If PSTO is in position "Off" or "Local", then no
changes are applied to the outputs.
Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO

Identification

Function Description
Elapsed time integrator
Description
Value when
activated
Output 1
1
Output 2
2
Output 3
4
Output 4
8
Output 5
16
Output 6
32
Output 7
64
Output 8
128
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
IEC 61850
IEC 60617
identification
identification
TEIGGIO
-
Section 13
Logic
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
ANSI/IEEE C37.2 device
number
-
465