Operation principle

The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the
eight outputs is activated based on the command sent from the operator place selected.
The settings Latchedx and tPulsex (where x is the respective output) will determine if
the signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will
block the operation of the function – in case a command is sent, no output will be
activated.
PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GGIO function.

Automation bits AUTOBITS

Identification

Function description
AutomationBits, command function for
DNP3

Functionality

The Automation bits function AUTOBITS is used to configure the DNP3 protocol
command handling. Each of the 3 AUTOBITS available has 32 individual outputs
available, each can be mapped as a binary output point in DNP3.
Step
Default
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
IEC 61850
identification
AUTOBITS
Section 12
Description
Setting for pulsed/latched mode for output
7
Output 7 Pulse Time
Setting for pulsed/latched mode for output
8
Output 8 pulse time
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
Control
-