Logic Diagram; Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 12
Control
12.3.2.4
12.3.2.5
356

Logic diagram

The function contains logic to enable the open and close commands respectively if the
interlocking conditions are fulfilled. That means also, if the switch being controlled
has its position defined as open (via POSOPEN) for example, then the appropriate
enable signal output (in this case EN_OPEN) is false. The switch operation enable
signals EN_OPEN and EN_CLOSE can be true at the same time only in the
intermediate and bad position state of the switch (defined via POSOPEN and
POSCLOSE) and if they are enabled by the interlocking function. The position inputs
come from the logical nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the
enable signals , OPEN_EN and CLOSE_EN come from the interlocking logic. The
outputs are connected to the logical node Switch controller (SCSWI). One instance
per switching device is needed.
POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN
IEC04000525 V1 EN
Figure 180:
SCILO function logic diagram

Signals

Table 235:
SCILO Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
OPEN_EN
BOOLEAN
CLOSE_EN
BOOLEAN
Table 236:
SCILO Output signals
Name
Type
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
=1
1
Default
Description
0
Open position of switch device
0
Closed position of switch device
0
Open operation from interlocking logic is enabled
0
Close operation from interlocking logic is enabled
Description
Open operation at closed or intermediate or bad
position is enabled
Close operation at open or intermediate or bad
position is enabled
1MRK 502 048-UEN A
SCILO
EN_OPEN
&
>1
&
EN_CLOSE
&
>1
&
en04000525.vsd
Technical manual