Signals; Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 9
Voltage protection
9.1.4
9.1.5
Table 156:
UV2PTUV Group settings (basic)
Name
Operation
OperationStep1
Characterist1
OpMode1
U1<
t1
t1Min
k1
Table continues on next page
258

Signals

Table 154:
UV2PTUV Input signals
Name
U3P
BLOCK
BLKST1
BLKST2
Table 155:
UV2PTUV Output signals
Name
TRIP
TR1
TR2
START
ST1
ST1L1
ST1L2
ST1L3
ST2

Settings

Values (Range)
Unit
Off
-
On
Off
-
On
Definite time
-
Inverse curve A
Inverse curve B
1 out of 3
-
2 out of 3
3 out of 3
1 - 100
%UB
0.00 - 6000.00
s
0.000 - 60.000
s
0.05 - 1.10
-
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
General trip signal
BOOLEAN
Trip signal from step 1
BOOLEAN
Trip signal from step 2
BOOLEAN
General start signal
BOOLEAN
Start signal from step 1
BOOLEAN
Start signal from step 1 phase L1
BOOLEAN
Start signal from step 1 phase L2
BOOLEAN
Start signal from step 1 phase L3
BOOLEAN
Start signal from step 2
Step
Default
-
Off
-
On
-
Definite time
-
1 out of 3
1
70
0.01
5.00
0.001
5.000
0.01
0.05
1MRK 502 048-UEN A
Description
Operation Off / On
Enable execution of step 1
Selection of time delay curve type for step
1
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 1
Voltage start value (DT & IDMT) in % of
UBase for step 1
Definite time delay of step 1
Minimum operate time for inverse curves
for step 1
Time multiplier for the inverse time delay
for step 1
Technical manual